400-600kVA Data Center PDU

C&C Power provides Power distribution Units (PDU) that are needed to power multiple server cabinets. This cabinet can support ratings from 400-600kVA. This stand-alone cabinet can ensure power protection for large co-location data centers, enterprise data centers, large healthcare facilities, financial institutions, utility systems, large manufacturing operations and more. Our PDU includes main breakers, individual breakers and a power monitoring system. An advanced monitoring package will be a standard inclusion on all models, will no left or ride side clearance required, making maintenance easy, for any data center layout. C&C power provides the most effective and flexible power distribution units to improve your organizations efficiency, uptime and growth.

 

Features
▶  Easy top, bottom and front wiring access with generous space for cabling
▶  Advanced main breaker monitoring package with sub-feed circuit monitoring
▶  No left or right side clearance required, only 6” rear clearance required for easy maintenance
▶  Most compact footprint on the market
▶  Fan-less convection cooled design with a door alarm
▶  Local and remote EPO, Modbus TCP and listed to UL60950-1
▶  Copper DOE 2016, K13 transformer is included

Optional Features
▶  Air Skirt
▶  Seismic Floor Stands for any location requirements
▶  Input/Output surge protection device, protecting voltage spikes
▶  Input power cabling junction box to provide a secure environment for electrical wires
▶  Branch circuit monitoring, allowing full utilization of your power infrastructure

 

Dimensions:
56.0″W x 42.0″D x 80.0″H
Input:
480 VAC, three-phase, 3-wire plus ground
Output:
208 VAC, three-phase, 4-wire plus ground or 400 VAC, three-phase, 4-wire plus ground
Transformer:
Copper, K13, DOE 2016 efficiency, 150 degrees Celsius rise, double shielded, 220 degrees Celsius insulation (class R)
Subfeed Breakers:
Up to (16) – 225A breakers of (6) 600A